Expérimentations sur le remplacement immédiat dans un cycle à pompe à chaleur utilisant le HFO-1234ze(E) et des mélanges de celui-ci avec le HFC-32.

Drop-in experiments on heat pump cycle using HFO-1234ze(E) and its mixtures with HFC-32.

Numéro : pap. n. R6, 2514

Auteurs : KOYAMA S., TAKATA N., FUKUDA S.

Résumé

In the present study we have carried out the drop-in experiments of R410A, HFO-1234ze(E) and the mixture of 50mass%HFO-1234ze(E)/50mass%HFC-32 at heating mode, using a vapor compression heat pump system developed for R410A. It has found that in the case of mixture of 50mass%HFO-1234ze(E)/50mass%HFC-32 the COP value is little affected by the degree of subcooling at the condenser outlet and it is only about 7.5% lower thanthat of R410A at the same heating load of 2.8 kW. This reveals that mixtures of HFO-1234ze(E)/HFC-32 are considered to be applicable as low-GWP alternatives for R410A by adjusting the composition of the mixture and by reconsidering the design parameters of components of room air-conditioning system.

Documents disponibles

Format PDF

Pages : 7 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Drop-in experiments on heat pump cycle using HFO-1234ze(E) and its mixtures with HFC-32.
  • Identifiant de la fiche : 30000556
  • Langues : Anglais
  • Source : 2010 Purdue Conferences. 13th International Refrigeration and Air-Conditioning Conference at Purdue.
  • Date d'édition : 12/07/2010