Influence d'une barrière rayonnante sur la charge de refroidissement dans les applications des maisons résidentielles des régions chaudes et arides : influence des conduits montés dans les combles.

Effect of a radiant barrier on the cooling load of a residential application in a hot and arid region: attic duct effect.

Auteurs : MOUJAES S. F., BRICKMAN R. A.

Type d'article : Article

Résumé

A computer simulation showed that an attic radiant barrier system significantly reduces cooling load requirements in hot desert climates. This reduction was due to both a reduction in sensible heat transfer through the ceiling and an even greater reduction in losses by the HVAC ducting system in the attic. These reductions were around 16% in runtime over the daytime hours and an overall 9% reduction over a five-day period. This latter effect indicates the need to improve current duct-loss calculation methods.

Détails

  • Titre original : Effect of a radiant barrier on the cooling load of a residential application in a hot and arid region: attic duct effect.
  • Identifiant de la fiche : 1999-3756
  • Langues : Anglais
  • Source : HVAC&R Research - vol. 4 - n. 3
  • Date d'édition : 07/1998