Document IIF

Influence de l'huile sur les performances d'un groupe frigorifique à compression.

Influence of oil on the operation of vapour-compression refrigeration systems.

Auteurs : LOTTIN O., GUILLEMET P., LEBRETON J. M., et al.

Résumé

Results concerning the response of refrigeration system simulation software to an increase of the amount of oil flowing with the refrigerant are presented. The effects of oil are found to be significant only when the quantity released by the compressor is above 0.5 to 1% of the refrigerant weight. Some conclusions are drawn concerning the optimum overheat control. In particular, it was shown that there were optima values for which either the exchanged power or the refrigeration COP is maximized.

Documents disponibles

Format PDF

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Influence of oil on the operation of vapour-compression refrigeration systems.
  • Identifiant de la fiche : 2004-1038
  • Langues : Anglais
  • Source : 21st IIR International Congress of Refrigeration: Serving the Needs of Mankind.
  • Date d'édition : 17/08/2003

Liens


Voir d'autres communications du même compte rendu (398)
Voir le compte rendu de la conférence