Résumé

The operation of a scroll compressor at high compression ratios can cause excessively high discharge temperatures, which can be detrimental to the reliability and efficiency of the compressor. In the present study, the performance of an inverter-driven scroll compressor with liquid refrigerant injection was measured with a variation of compressor frequency, injection pressure, and injection location. The influence of the liquid injection on the performance is presented as a function of operating parameters and injection location by comparing the results with those for the non-injection case. It was found that liquid injection under high frequency was very effective at attaining higher performance and reliability of the compressor, but injection under low frequency showed some disadvantages. For high frequency at a given injection ratio, the injection at alpha=180°, for an injection angle at an injection port, yielded slightly better performance of the compressor as compared to that at alpha=90°.

Documents disponibles

Format PDF

Pages : 87-94

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Influence of liquid refrigerant injection on the performance of an inverter-driven scroll compressor.
  • Identifiant de la fiche : 2003-1777
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 26 - n. 1
  • Date d'édition : 01/2003

Liens


Voir d'autres articles du même numéro (14)
Voir la source