INFLUENCE DE LA RESISTANCE THERMIQUE DE CONTACT INTERNE SUR LA PERFORMANCE THERMIQUE D'UN TUBE DOUBLE FRETTE.

THE INFLUENCE OF INTERFACE THERMAL CONTACT RESISTANCE ON THE HEAT TRANSFER PERFORMANCE OF PRESTRESSED DUPLEX TUBE.

Auteurs : BARBER J. R.

Type d'article : Article

Résumé

LE TUBE DOUBLE FRETTE POUR ECHANGEUR DE CHALEUR EST CONSTITUE DE DEUX CYLINDRES CONCENTRIQUES ASSEMBLES DANS UN ETAT DE PRECONTRAINTE. LORS DE L'UTILISATION, LA DILATATION THERMIQUE CHANGE LA PRESSION A L'INTERFACE ET CECI CAUSE UN ACCROISSEMENT SENSIBLE DE LA RESISTANCE THERMIQUE DU TUBE. DANS CERTAINES CIRCONSTANCES, ON PEUT OBTENIR PLUS D'UNE SOLUTION DE REGIME PERMANENT. ON ANALYSE L'EFFET DE CE MECANISME SUR LA VARIATION DE TEMPERATURE AXIALE DANS LES ECHANGEURS DE CHALEUR EN ECOULEMENTS PARALLELES, A CO-COURANT OU CONTRE-COURANT. ON DEVELOPPE UNE METHODE POUR INTEGRER SANS ITERATION LES EQUATIONS DANS LE CAS D'UNE RESISTANCE THERMIQUE DE CONTACT ARBITRAIRE, NON LINEAIRE, DEPENDANT DE LA PRESSION, ET ON DISCUTE L'EFFET DE LA PRECONTRAINTE ET DES AUTRES PARAMETRES SUR LA POSSIBILITE DE SOLUTIONS MULTIPLES.

Détails

  • Titre original : THE INFLUENCE OF INTERFACE THERMAL CONTACT RESISTANCE ON THE HEAT TRANSFER PERFORMANCE OF PRESTRESSED DUPLEX TUBE.
  • Identifiant de la fiche : 1986-2241
  • Langues : Anglais
  • Source : International Journal of Heat and Mass Transfer - vol. 29 - n. 5
  • Date d'édition : 1986

Liens


Voir d'autres articles du même numéro (3)
Voir la source