Influence des dispositions non-uniformes de garnissages sur les performances thermiques dans une tour de refroidissement humide.
Influence of non-uniform layout fillings on thermal performance for wet cooling tower.
Auteurs : GAO M., ZHANG L., WANG N. N., et al.
Type d'article : Article
Résumé
Based on the similarity theory, thermal-state model experiment in lab is performed to investigate the thermal performance of wet cooling towers under different layout patterns of fillings, and five kinds of layout patterns, including uniform layout and four kinds of non-uniform layout patterns, are studied in this paper. Experimental results manifest that the thermal performance of wet cooling towers under non-uniform layout patterns is outstanding by calculating and analyzing five performance parameters, which are ooling termperature difference, cooling efficiency, Merkel number, Lewis number and the ratio of evaporative heat rejection. Additionally, research also obtained the optimal three-block layout pattern of fillings in which the radius ratio of ra/rc is approximately 0.44 and rb/rc is around 0.71; here ra, rb and rc are the radius of three blocks, respectively. What's more, compared with the uniform layout pattern of fillings, the thermal performance of the optimal layout pattern can enhance by 30% at maximum within the scope of this test.
Détails
- Titre original : Influence of non-uniform layout fillings on thermal performance for wet cooling tower.
- Identifiant de la fiche : 30017038
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 93
- Date d'édition : 25/01/2016
- DOI : http://dx.doi.org/10.1016/j.applthermaleng.2015.09.054
Liens
Voir d'autres articles du même numéro (72)
Voir la source
Indexation
-
A simplified method on thermal performance capa...
- Auteurs : ASVAPOOSITKUL W.
- Date : 05/2012
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 38
Voir la fiche
-
Numerical analysis of solar enhanced natural dr...
- Auteurs : ZHOU Z., GONG H.
- Date : 05/02/2016
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 94
Voir la fiche
-
Experimental determination of drift loss from a...
- Auteurs : LUCAS M., MARTÍNEZ P. J., VIEDMA A.
- Date : 09/2012
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 35 - n. 6
- Formats : PDF
Voir la fiche
-
Enhancement of cooling capacity in a hybrid clo...
- Auteurs : SARKER M. M. A., SHIM G. J., LEE H. S., et al.
- Date : 11/2009
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 29 - n. 16
Voir la fiche
-
Experimental investigation on the performance o...
- Auteurs : NING T., CHONG D., JIA M., et al.
- Date : 03/2015
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 78
Voir la fiche