Résumé

This paper investigates the energy efficiency of geothermal storage integration into the state-of-the-art CO2 transcritical booster systems. Three scenarios of integration are studied including stand-alone and integrated supermarket building systems. The results show that for a stand-alone supermarket, heat recovery from the CO2 system should be prioritized over extracting heat from the ground, which this heat extraction can be done either by an extra evaporator in the CO2 system or by a separate ground source heat pump. In the case of supermarket integration with a nearby district heating consumer, geothermal storage integration with
extra evaporator in the CO2 refrigeration system can reduce the total annual running cost of the two buildings by 19-31% and with a payback time of less than three years. This integration is beneficial if the full efficient heat recovery capacity of the CO2 system is not sufficient to provide the entire demands.

Documents disponibles

Format PDF

Pages : 8

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Integration of supermarket’s CO2 refrigeration system and geothermal storage.
  • Identifiant de la fiche : 30026429
  • Langues : Anglais
  • Source : Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
  • Date d'édition : 24/08/2019
  • DOI : http://dx.doi.org/10.18462/iir.icr.2019.0570

Liens


Voir d'autres communications du même compte rendu (632)
Voir le compte rendu de la conférence