LA GRANDE RENTABILITE DE L'ACCUMULATION DE FROID DANS LES NOUVEAUX IMMEUBLES COMMERCIAUX.

THE HIGH COST-EFFECTIVENESS OF COOL STORAGE IN NEW COMMERCIAL BUILDINGS.

Résumé

LA STRATEGIE LE MEILLEUR MARCHE, L'ACCUMULATION PARTIELLE, DEPLACE LES DEUX TIERS DE LA DEMANDE DE FROID ET PEUT DEPLACER 3 GW PAR AN DANS LES NOUVEAUX BATIMENTS AMERICAINS. LA STRATEGIE PLUS COUTEUSE POUR EVITER LA DEMANDE TOTALE PEUT DEPLACER ENCORE 2 GW. L'ACCUMULATION PARTIELLE UTILISE UN REFROIDISSEUR PREVU POUR LE FONCTIONNEMENT CONTINU. LES NUITS D'ETE, LA PUISSANCE DU REFROIDISSEUR EN EXCEDENT EST UTILISEE POUR ACCUMULER DU FROID, PUIS CE FROID EST UTILISE L'APRES-MIDI SUIVANT. L'ACCUMULATION LIMITEE PAR LA DEMANDE REDUIT LES FRAIS DE FONCTIONNEMENT PAR INSTALLATION D'UN REFROIDISSEUR PREVU POUR ETRE ARRETE LORSQUE L'ELECTRICITE EST LE PLUS CHER. LE REFROIDISSEUR ET L'ACCUMULATION DOIVENT ETRE DE DIMENSIONS SUPERIEURES D'ENVIRON 40 % A CE QUI SERAIT EXIGE POUR L'ACCUMULATION PARTIELLE. DU POINT DE VUE DE LA SOCIETE ET DES SERVICES PUBLICS, EVITER LES PERIODES DE POINTE ECONOMISERA A LA LONGUE DE L'ARGENT ET DES CENTRALES ELECTRIQUES.

Détails

  • Titre original : THE HIGH COST-EFFECTIVENESS OF COOL STORAGE IN NEW COMMERCIAL BUILDINGS.
  • Identifiant de la fiche : 1987-0344
  • Langues : Anglais
  • Date d'édition : 1985
  • Source : Source : ASHRAE Trans.
    vol. 91; n. 2B; 818-832; 9 fig.; 5 tabl.; 6 ref.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.