LA MODERNISATION DE L'ACCUMULATION THERMIQUE AU SERVICE D'UN SYSTEME A DEUX TEMPERATURES.

THERMAL STORAGE RETROFIT RESTORES DUAL TEMPERATURE SYSTEM.

Auteurs : HOLNESS G. V. R.

Résumé

L'INTEGRATION DE L'ACCUMULATION THERMIQUE AU SYSTEME EXISTANT DE CHAUFFAGE ET DE REFROIDISSEMENT A DEUX TEMPERATURES A PERMIS DE REPONDRE AUX EXIGENCES D'UNE EXTENSION D'INSTALLATIONS DE PRODUCTION INDUSTRIELLE, TOUT EN AMELIORANT LA PERFORMANCE DU SYSTEME. UNE CENTRALE FRIGORIFIQUE ACTUELLE DE 17.600 KILOWATTS COMPRENAIT 2 REFROIDISSEURS CENTRIFUGES A TURBINE A VAPEUR DE 3.000 KILOWATTS COMPLETANT 2 REFROIDISSEURS A ABSORPTION DE 5.000 KILOWATTS. L'EXIGENCE D'UNE AUGMENTATION DE LA PUISSANCE DE 7.000 KILOWATTS ET LE BESOIN D'UNE REGULATION DE L'ENVIRONNEMENT RIGOUREUSE ONT ENTRAINE LA NECESSITE DE RENOVER ENTIEREMENT LE SYSTEME. LE COUT D'INVESTISSEMENT DE L'INSTALLATION CORRESPONDAIT, A5 % PRES, AUX ESTIMATIONS INITIALES. CEPENDANT, LE COUT REEL DE LA CENTRALE INSTALLEE A ACCUSE UNE HAUSSE DE 8 % DE PLUS A CAUSE DES CONDITIONS LOCALES. LE SYSTEME D'ACCUMULATION THERMIQUE LUI-MEME A ETE MIS AU POINT SANS PROBLEMES MAJEURS, LES PLUS IRTT NT'EO EEE. RE CONSIDEREE COMME PARTIE INTEGRANTE DE LA CONCEPTION DU SYSTEME. EN MEME TEMPS, ELLE PRESENTE LES AVANTAGES SUIVANTS : PLUS GRANDE STABILITE DE FONCTIONNEMENT ET FIABILITE DE LA CENTRALE ET COUTS DE FONCTIONNEMENT REDUITS GRACE AUX ECONOMIES DE CONSOMMATION D'ELECTRICITE.

Détails

  • Titre original : THERMAL STORAGE RETROFIT RESTORES DUAL TEMPERATURE SYSTEM.
  • Identifiant de la fiche : 1989-1166
  • Langues : Anglais
  • Date d'édition : 1988
  • Source : Source : ASHRAE Trans.
    vol. 94; n. 1; 1866-1878; 5 fig.; 4 phot.; 7 ref.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.