Recommandé par l'IIF

Le R468C comme substitut à faible PRP au R410A dans les évaporateurs tubes ailetés. 

R468C as a Low-GWP replacement of R410A in fin-and-tube evaporators.

Numéro : 2262

Auteurs : GHADIRI M., BACH C. K., BRADSHAW C. R.

Résumé

Using common refrigerants such as R410A in air conditioning systems leads to climate change due to their high global warming potential (GWP). Therefore, restrictive laws have been enacted to force manufacturers to use refrigerants with lower GWP than that of R410A. This simulation study explores the effects of substituting R410A with R468C on the performance of a fin-and-tube evaporator coil. A validated segment-by-segment heat exchanger model is used to find the optimum performance of using R468C as a working fluid by changing the heat exchanger circuitries. The results show that for identical superheat temperature (SHT) and saturated suction temperature (SST), R468C required a higher refrigerant flow rate, resulting in an increased cooling capacity (between 30-57%) and a lower coefficient of performance (about 10%) than R410A.

Documents disponibles

Format PDF

Pages : 10 p.

Disponible

Gratuit

Détails

  • Titre original : R468C as a Low-GWP replacement of R410A in fin-and-tube evaporators.
  • Identifiant de la fiche : 30030257
  • Langues : Anglais
  • Source : 2022 Purdue Conferences. 19th International Refrigeration and Air-Conditioning Conference at Purdue.
  • Date d'édition : 10/07/2022
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres communications du même compte rendu (224)
Voir le compte rendu de la conférence