Document IIF

Le rôle des compresseurs dans les installations frigorifiques industrielles : une analyse exergétique.

The role of compressors in industrial refrigerating plants: an exergy analysis.

Résumé

An exergy analysis is developed for three reference refrigerating plants representative for a large number of plants commonly encountered in The Netherlands. The main goal is to identify the share of the compressor losses in the total losses of refrigerating plants and to come to quantification of acceptable isentropic efficiency levels. The role of the compressor exergy losses is negligible for applications where the running time is small and the isentropic efficiency of the compressor is larger than 60%. Applications with large running times require isentropic efficiencies of 70 to 80% to obtain acceptable compressor exergy losses.

Documents disponibles

Format PDF

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : The role of compressors in industrial refrigerating plants: an exergy analysis.
  • Identifiant de la fiche : 2000-1169
  • Langues : Anglais
  • Source : 20th International Congress of Refrigeration: Refrigeration into the Third Millennium.
  • Date d'édition : 19/09/1999

Liens


Voir d'autres communications du même compte rendu (447)
Voir le compte rendu de la conférence