Document IIF

Mauvaise distribution dans des évaporateurs de pompe à chaleur air-eau. 1. Effets sur l'évaporateur, la pompe à chaleur et le niveau du système.

Maldistribution in air–water heat pump evaporators. 1. Effects on evaporator, heat pump and system level.

Auteurs : MADER G., PALM B., ELMEGAARD B.

Type d'article : Article, Article de la RIF

Résumé

This paper presents an approach to quantify the effect of evaporator maldistribution on operating costs of air–water heat pumps. In the proposed simulation model maldistribution is induced by two parameters describing refrigerant phase and air flow distribution. Annual operating costs are calculated based on heat pump performance at distinct operating conditions. Results show that percentage increase of operating costs is similar for the three considered climate zones, even though the effect of maldistribution on heat pump performance varies with operating conditions. Differences in terms of absolute cost increase for the climate zones arise mainly due to a varying number of operating hours. Absolute cost increase is considerable in the average and especially colder climate zone and can only partly be reduced by enlarging the evaporator.

Documents disponibles

Format PDF

Pages : 207-216

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Maldistribution in air–water heat pump evaporators. 1. Effects on evaporator, heat pump and system level.
  • Identifiant de la fiche : 30013581
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 50
  • Date d'édition : 02/2015

Liens


Voir d'autres articles du même numéro (20)
Voir la source