Résumé

CET ARTICLE TRAITE DES TECHNIQUES D'ANALYSE PAR LE DEUXIEME PRINCIPE DE LA THERMODYNAMIQUE APPLIQUEES AU CALCUL DE L'ENERGIE SENSIBLE DE REFRIGERATION DES UNITES DE STOCKAGES A PAROIS NON ADIABATIQUES. LE CALCUL EST BASE SUR LA MINIMISATION DE L'ENTROPIE CREEE PAR UN ECART FINI DE TEMPERATURE. LES RESULTATS DE CETTE ETUDE METTENT EN EVIDENCE 3 POINTS FONDAMENTAUX : 1) LE TAUX D'IRREVERSIBILITE EST PLUS GRAND EN PRESENCE QU'EN ABSENCE DE FUITES THERMIQUES ; 2) L'ACCROISSEMENT DE L'IRREVERSIBILITE DU AUX FUITES THERMIQUES DIMINUE EXPONENTIELLEMENT LE COEFFICIENT EFFECTIF DE TRANSFERT ; 3) IL EXISTE UN PARAMETRE, SANS DIMENSION, FAISANT INTERVENIR LE TEMPS ET DEUX AUTRES PARAMETRES FONDAMENTAUX, EGALEMENT SANS DIMENSION, QUI PERMET DE MAXIMISER L'ENERGIE STOCKEE UTILE.