Mesure de la concentration d'huile au niveau du refoulement d'un compresseur frigorifique.

Oil concentration measurement at discharge line of refrigerant compressor.

Résumé

Real-time measurement of oil amount flowing out from a compressor with refrigerant gas is required to examine the reliability of the compressor and the transient oil behaviour in the refrigeration cycle. In the study, an optical method to measure the oil concentration at the compressor discharge line is investigated experimentally. A photo-sensor unit consisting of a LED and a photodiode detects the intensity of light transmitted through a glass tube in which the compressor discharge refrigerant mixed with oil flows. By experiment, it is found that the flow pattern in the compressor discharge line is the annular flow of oil film. The photo-sensor output varies depending on the oil flow rate rather than on the oil concentration in the refrigerant flow. The sensor output is correlated to the oil flow rate though the correlation is slightly influenced by the flow direction and the light axis direction.

Détails

  • Titre original : Oil concentration measurement at discharge line of refrigerant compressor.
  • Identifiant de la fiche : 2007-0611
  • Langues : Anglais
  • Source : ACRA-2006. Proceedings of the 3rd Asian conference on refrigeration and air conditioning.
  • Date d'édition : 21/05/2006

Liens


Voir d'autres communications du même compte rendu (161)
Voir le compte rendu de la conférence