Mesure de la perte faible de la concentration d'huile d'un mélange frigorigène/huile dans une conduite de liquide.

Low loss measurement of oil concentration in a refrigerant-oil mixture in a liquid line.

Auteurs : MCGOVERN J. A.

Type d'article : Article, Article de la RIF

Résumé

A method of measuring the mass concentration of lubricating oil in a refrigerant-oil mixture in a liquid line within a refrigeration system is described. It is suitable for use where the oil and refrigerant are fully miscible in the liquid phase, e.g. for mineral oil and R12. The technique involves taking a small liquid sample, measuring its volume, venting the refrigerant back into the system and weighing the residual oil. Many measurements can be made, with negligible loss of refrigerant from the system. An application of the method to a split circuit bypass type compressor load stand is also described.

Documents disponibles

Format PDF

Pages : 310-313

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Low loss measurement of oil concentration in a refrigerant-oil mixture in a liquid line.
  • Identifiant de la fiche : 30001724
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 12 - n. 6
  • Date d'édition : 11/1989