MESURE DU DEVELOPPEMENT ET DE LA DENSITE DU GIVRE DANS UNE GEOMETRIE DE PLAQUES PARALLELES.

MEASUREMENT OF FROST GROWTH AND DENSITY IN A PARALLEL PLATE GEOMETRY.

Résumé

ON A ENTREPRIS UNE RECHERCHE EXPERIMENTALE POUR DETERMINER L'INFLUENCE DU NOMBRE DE REYNOLDS, DE L'HUMIDITE DE L'AIR, DE LA TEMPERATURE DE L'AIR ET DE LA TEMPERATURE DES PLAQUES SUR LE DEVELOPPEMENT ET LA DENSITE DU GIVRE SUR UNE PLAQUE VERTICALE DANS UNE GEOMETRIE D'ECOULEMENT PARALLELE. LE DEVELOPPEMENT DU GIVRE AUGMENTAIT EN FONCTION DES NOMBRES DE REYNOLDS LORSQUE CEUX-CI ETAIENT INFERIEURS A 15.900. AU-DESSUS DE CETTE VALEUR LE NOMBRE DE REYNOLDS N'AVAIT PAS D'INFLUENCE. LE DEVELOPPEMENT DEPENDAIT FORTEMENT DE LA TEMPERATURE DES PLAQUES D'ECHANGEUR DE CHALEUR ET DE L'HUMIDITE RELATIVE DE L'AIR. UNE CORRELATION EMPIRIQUE ENTRE L'EPAISSEUR DE GIVRE ET LE TEMPS, LE NOMBRE DE REYNOLDS, LA TEMPERATURE DES PLAQUES ET L'HUMIDITE DE L'AIR A ETE ETABLIE. LA DENSITE DU GIVRE AUGMENTAIT EN FONCTION DU TEMPS ET DU NOMBRE DE REYNOLDS.

Détails

  • Titre original : MEASUREMENT OF FROST GROWTH AND DENSITY IN A PARALLEL PLATE GEOMETRY.
  • Identifiant de la fiche : 1985-2384
  • Langues : Anglais
  • Date d'édition : 1984
  • Source : Source : ASHRAE Trans.
    vol. 90; n. 2A; 278-290; 11 fig.; 4 tabl.; 17 ref.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.