Mesures de la puissance thermique spécifique du HFE-347pcf2 grâce à un calorimètre mesurant l'écoulement.

Measurements of specific heat capacity of gaseous HFE-347pcf2 using a flow calorimeter.

Résumé

The specific isobaric heat capacity was measured for HFE-347pcf2 (1,1,2,2-tetrafluoroethyl-2,2,2-trifluoroethylether) in the gas phase. HFE 347pcf2 has a lower GWP value of 580 and is one of new environmentally-friendly solvents and potential refrigerants. Eleven measurements for HFE-347pcf2 were primarily obtained at temperatures from 318 to 363 K and at pressures from 0.05 to 0.17 MPa. The expanded uncertainty (k= 2) of the temperature measurements is estimated to be less 78 mK, and that of the pressure measurements is less 16.5 kPa. The expanded uncertainty for heat capacity, is estimated to range around 31 J/kg.K.

Documents disponibles

Format PDF

Pages : pp. 567-571

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Measurements of specific heat capacity of gaseous HFE-347pcf2 using a flow calorimeter.
  • Identifiant de la fiche : 2010-0722
  • Langues : Anglais
  • Source : ACRA-2009. The proceedings of the 4th Asian conference on refrigeration and air conditioning: May 20-22, 2009, Taipei, R.O.C.
  • Date d'édition : 20/05/2009

Liens


Voir d'autres communications du même compte rendu (102)
Voir le compte rendu de la conférence