Mesures expérimentales sur la rétention d'huile pendant la condensation et l'évaporation du frigorigène dans un écoulement diphasique.

Experimental measurement of oil hold-up during refrigerant condensation and evaporation in two phase flow.

Numéro : pap. n. R24, 2488

Auteurs : ALONSO M., JASSIM E. W., NEWELL T. A.

Résumé

This paper presents the effects of heat transfer on oil hold-up in smooth, axially finned, and 18° helically finned 8.915mm I.D. horizontal tubes under evaporation and condensation conditions with a R134a /ISO32 polyol ester refrigerant oil mixture. Heat fluxes ranging from 4000 to 6000 W/m2 were applied through a water jacket. The tests were conducted at a saturation temperature of 25°C, at mass fluxes of 100 to 300 kg/m2-s, and a range of average qualities from 20-95%, oil flow concentration varied from 3-5.5%. Oil hold-up is observed to reach a minimum value in the mid-range qualities, but increases at higher qualities. In general, the enhanced tubes exhibit higher oil hold-up compared to the smooth tube, but enhanced tube trends differ between condensation and evaporation based on enhancement. The addition of oil is found to decrease condensation heat transfer while increasing evaporative heat transfer at lower and mid-range qualities.

Documents disponibles

Format PDF

Pages : 8 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental measurement of oil hold-up during refrigerant condensation and evaporation in two phase flow.
  • Identifiant de la fiche : 30000987
  • Langues : Anglais
  • Source : 2010 Purdue Conferences. 13th International Refrigeration and Air-Conditioning Conference at Purdue.
  • Date d'édition : 12/07/2010

Liens


Voir d'autres communications du même compte rendu (121)
Voir le compte rendu de la conférence