Méthode de détection de la composition en circulation dans un cycle frigorifique utilisant le mélange zéotropique de frigorigènes R407C.

[In Japanese. / En japonais.]

Auteurs : SUMIDA Y., OKAZAKI T., UENO Y.

Type d'article : Article

Résumé

A composition sensing circuit (CS circuit), which detects the circulating composition of the ternary zeotropic refrigerant mixture R407C in a refrigeration cycle has been developed. The CS circuit consists of a heat exchanger, a capillary tube, two temperature detectors and one pressure detector. The circulating composition is calculated from the temperature and pressure in the circuit and the vapour liquid equilibrium for R32- R125- R134a mixtures together with the approximated relation between mass fractions of R32 and R125. The experiments were also carried out to evaluate the accuracy of calculation: the results are good.

Détails

  • Titre original : [In Japanese. / En japonais.]
  • Identifiant de la fiche : 2002-1739
  • Langues : Japonais
  • Source : Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers - vol. 18 - n. 3
  • Date d'édition : 2001
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres articles du même numéro (30)
Voir la source