Résumé

This article presents a system simulation model of an oil-injected screw chiller. The refrigerant (shell and tube) heat exchangers were modelled, using a three-zone approach, to study the effects of the operational parameters on the fractional area allocated to each phase within the heat exchangers. All major components of the system such as, an oil-injected screw compressor, a shell-and-tube condenser, a flooded evaporator and a high-side-float valve, were modelled in a modular format. The predicted results were validated with experimental data collected from a multiple-chiller plant in a process plant. The results show that the part-load ratio and the temperature of glycol-water entering the evaporator affect the system performance significantly and have a strong influence on the fractional areas allocated to each phase within the condenser.

Détails

  • Titre original : Three-zone system simulation model of a multiple-chiller plant.
  • Identifiant de la fiche : 2005-0950
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 24 - n. 14-15
  • Date d'édition : 10/2004

Liens


Voir d'autres articles du même numéro (13)
Voir la source