Modèle de simulation dynamique utilisé pour la performance transitoire d'un refroidisseur de liquide. 1. Le modèle.

A dynamic simulation model for transient absorption chiller performance. 1. The model.

Auteurs : KOHLENBACH P., ZIEGLER F.

Type d'article : Article, Article de la RIF

Résumé

This paper is the first of two which presents the development of a dynamic model for single-effect LiBr/water absorption chillers. The model is based on external and internal steady-state enthalpy balances for each main component. Dynamic behaviour is implemented via mass storage terms in the absorber and generator, thermal heat storage terms in all vessels and a delay time in the solution cycle. A special feature is that the thermal capacity is partly connected to external and partly to internal process temperatures. In this paper, the model is presented in detail. For verification, the model has been compared to experimental data. The dynamic agreement between experiment and simulation is very good with dynamic deviations around 10 s. General functionality of the model and a more detailed comparison with experimental data are presented in Part II of this paper (see this Bulletin, reference 2008-0635).

Documents disponibles

Format PDF

Pages : 217-225

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : A dynamic simulation model for transient absorption chiller performance. 1. The model.
  • Identifiant de la fiche : 2008-0634
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 31 - n. 2
  • Date d'édition : 03/2008