Document IIF

Modèle empirique pour la prévision de l'infiltration d'air vers l'intérieur des entrepôts frigorifiques via les portes.

An empirical model for predicting air infiltration into refrigerated stores through doors.

Auteurs : CHEN P., CLELAND D. J., LOVATT S. J., et al.

Type d'article : Article, Article de la RIF

Résumé

An empirical model based on Tamm's equation was developed to predict the rate of air infiltration through doors into refrigerated buildings. The model sums the contributions of air-tightness, air infiltration due to door opening and the additional air exchange caused by forklift traffic through the doors. The model was validated against measured air infiltration rates through rapid-roll and sliding doors into 7 commercial cold stores with sizes ranging from 740 to 12,000 m3 operating at temperatures ranging from 3.3 to -21.8 °C.

Documents disponibles

Format PDF

Pages : 799-812

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : An empirical model for predicting air infiltration into refrigerated stores through doors.
  • Identifiant de la fiche : 2003-0907
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 25 - n. 6
  • Date d'édition : 09/2002

Liens


Voir d'autres articles du même numéro (12)
Voir la source