Document IIF
Modélisation d'un refroidisseur évaporatif à régénération indirecte pour un système de refroidissement à déshydratant.
Modeling of a regenerative indirect evaporative cooler for a desiccant cooling system.
Numéro : pap. n. TP-088
Auteurs : BELLEMO L., ELMEGAARD B., REINHOLDT L. O., et al.
Résumé
This paper presents a numerical study of a regenerative indirect evaporative cooler, the so-called Dew Point Cooler (DPC), which is part of a Desiccant Cooling system that may both dehumidify and cool humid air. The DPC model is based on first principles using a 1D finite volume scheme and determines the steady state working conditions for the component. A sensitivity analysis of the DPC performance is carried out based on the air inlet conditions, air flow rate and recirculation fraction. A recirculation fraction around 0.3 maximizes the DPC net cooling capacity. The supply temperature is found to be mostly affected by the inlet humidity ratio. Manufacturer data are used to tune the model. The tuned DPC model is characterized by an area effectiveness coefficient which is kept constant at 0.55. The cooling capacity and water consumption estimated by the tuned model deviate within 3% and 8%, respectively from manufacturer data. The computed pressure drops deviates within 6% from manufacturer data.
Documents disponibles
Format PDF
Pages : 9 p.
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Modeling of a regenerative indirect evaporative cooler for a desiccant cooling system.
- Identifiant de la fiche : 30008315
- Langues : Anglais
- Source : 4th IIR Conference on Thermophysical Properties and Transfer Processes of Refrigerants
- Date d'édition : 17/06/2013
Liens
Voir d'autres communications du même compte rendu (69)
Voir le compte rendu de la conférence
-
Development of a novel desiccant chiller with r...
- Auteurs : DAI Y. J., LA D., LI H., et al.
- Date : 06/04/2011
- Langues : Anglais
- Source : Sources/sinks Alternative to the Outside Air for Heat Pump and Air-conditioning Techniques (Alternative Sources - AS), Padua, Italy, April 5-7, 2011. / International Sorption Heat Pump Conference (ISHPC11), Padua, Italy, April 6-8, 2011.
- Formats : PDF
Voir la fiche
-
Komponenten- und Anlagenverhalten solar betrieb...
- Auteurs : EICKER U., HUBER M., SCHÜRGER U., et al.
- Date : 11/2002
- Langues : Allemand
- Source : KI Luft Kältetech. - vol. 38 - n. 11
Voir la fiche
-
Use of regenerative evaporative cooling to impr...
- Auteurs : LA D., DAI Y. J., LI Y., et al.
- Date : 09/2012
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 42
Voir la fiche
-
Experimental study on combined low temperature ...
- Auteurs : ARUN B. S., MARIAPPAN V., MAISOTSENKO V.
- Date : 04/2020
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 112
- Formats : PDF
Voir la fiche
-
Novel desiccant cooling system using indirect e...
- Auteurs : BELDING W. A., DELMAS M. P. F.
- Date : 1997
- Langues : Anglais
- Source : ASHRAE Transactions.
Voir la fiche