Nouveau système à saumure pour une patinoire.
New brine system for skating rink.
Auteurs : DUMAS C.
Type d'article : Article
Résumé
In order to avoid corrosion problems and to reduce energy consumption, modifications were performed. First, the brine specification was updated. Then the two-pass brine distribution systems with evaporators connected in parallel was replaced with a four-pass brine distribution system with evaporators in series. Brine flow was reduced by 50% and pump horsepower by 40%, while maintaining sufficient fluid velocity in the heat exchangers.
Détails
- Titre original : New brine system for skating rink.
- Identifiant de la fiche : 2001-0543
- Langues : Anglais
- Source : ASHRAE Journal - vol. 41 - n. 8
- Date d'édition : 08/1999
Liens
Voir d'autres articles du même numéro (3)
Voir la source
Indexation
- Thèmes : Patinoires, neige artificielle
- Mots-clés : Canada; Modernisation; Saumure; Patinoire; Corrosion; Circuit hydraulique
-
La piste de glace du championnat Red Bull Crash...
- Auteurs : TREMBLAY G.
- Date : 03/2010
- Langues : Français
- Source : Climapresse - vol. 17 - n. 2
Voir la fiche
-
La piste de patinage du "Barcça" (Club de Footb...
- Auteurs : PADROS-COROMINAS F.
- Date : 12/1993
- Langues : Espagnol
- Source : Refrig. Frial - n. 29
Voir la fiche
-
Existing ice rink uses CO2 system.
- Auteurs : SIMARD L.
- Date : 03/2012
- Langues : Anglais
- Source : ASHRAE Journal - vol. 54 - n. 3
Voir la fiche
-
Remplacement du R22 ? Les fluides caloporteurs.
- Date : 05/2007
- Langues : Français
- Source : Rencontres Patinoires, Mont Dore - 29 p.; fig.; tabl.
Voir la fiche
-
Refrigerant 410A takes to the ice.
- Auteurs : POWELL P.
- Date : 01/04/2002
- Langues : Anglais
- Source : Air Cond. Heat. Refrig. News/achrnews.com - 3 p.
Voir la fiche