Optimisation des refroidisseurs à absorption.
Optimizing absorption chillers.
Auteurs : MECKLER M.
Type d'article : Article
Résumé
Triple-effect or even four-effect direct-fired absorption (DFA) chillers are unlikely to find support in the US utility marketplace because of their high first-cost premiums and oversized footprints. Furthermore, chilled water temperature difference is reduced and piping is increased. Describes how, by integrating a novel design feature - the vapour recompression absorber, powered by a relatively small electric motor within a conventional DFA chiller cycle - a hybrid dual-absorber cycle is achieved with lower first costs and smaller footprints.
Détails
- Titre original : Optimizing absorption chillers.
- Identifiant de la fiche : 2000-2116
- Langues : Anglais
- Source : Consult. Specif. Eng. - vol. 25 - n. 1
- Date d'édition : 01/1999
Liens
Voir d'autres articles du même numéro (2)
Voir la source
Indexation
-
Chiller prime movers.
- Auteurs : LIEGOIS W.
- Date : 03/2000
- Langues : Anglais
- Source : HPAC Engineering - vol. 72 - n. 3
Voir la fiche
-
New developments in hybrid natural gas/electric...
- Auteurs : NOWAKOWSKI G. A., GRAMLICH M.
- Date : 09/1999
- Langues : Anglais
- Source : ASHRAE Journal - vol. 41 - n. 9
Voir la fiche
-
UN REFROIDISSEUR-RECHAUFFEUR D'EAU MONOBLOC UTI...
- Auteurs : YOSHIKAWA M.
- Date : 1985
- Langues : Japonais
- Source : Refrigeration - vol. 60 - n. 690
Voir la fiche
-
Payback evaluation for an absorption chiller/CH...
- Auteurs : JONES A.
- Date : 08/1998
- Langues : Anglais
- Source : Build. Serv. J. - vol. 20 - n. 8
Voir la fiche
-
Operation and maintenance considerations for ga...
- Auteurs : RECTOR J. D.
- Date : 1997
- Langues : Anglais
- Source : J. Energy Eng. - vol. 94 - n. 1
Voir la fiche