PERFORMANCE ANNUELLE D'UNE POMPE A CHALEUR RELIEE AU SOL, A SERPENTINS HORIZONTAUX.

ANNUAL PERFORMANCE OF A HORIZONTAL-COIL GROUND-COUPLED HEAT PUMP.

Auteurs : JOHNSON W. S.

Résumé

ON A MESURE POUR LES SAISONS DE REFROIDISSEMENT ET DE CHAUFFAGE LA PERFORMANCE D'UNE POMPE A CHALEUR RELIEE AU SOL. LES MESURES HORAIRES DES FLUX THERMIQUES, DES CONSOMMATIONS D'ENERGIE ET DES DIVERSES TEMPERATURES DU SOL, DE L'ESPACE ET DU SYSTEME ONT ETE ENREGISTREES ETANALYSEES POUR DONNER LA PERFORMANCE SAISONNIERE GLOBALE. POUR LA SAISON DE CHAUFFAGE, ON A TROUVE QUE LE FACTEUR DE PERFORMANCE ETAIT DE 2,6, CE QUI EST SUPERIEUR A CELUI D'UN SYSTEME AIR-AIR TYPIQUE, ET POUR LA SAISON DE REFROIDISSEMENT DE 1,1 SEULEMENT, CE QUI EST TRES INFERIEUR A CELUI D'UN SYSTEME AIR-AIR TYPIQUE. LES RAISONS DE CETTE FAIBLE PERFORMANCE POUR CE MODE DE FONCTIONNEMENT SONT, ENTRE AUTRES, UNE MAUVAISE METHODE DE REMBLAYAGE LORSQUE LE SERPENTIN AU SOL A ETE ENTERRE, LA DESSICCATION DU SOL ET PEUT-ETRE UN SERPENTIN ENTERRE TROP COURT. DE PLUS, LA POMPE A CHALEUR ELLE-MEME A UN COP FAIBLE.

Détails

  • Titre original : ANNUAL PERFORMANCE OF A HORIZONTAL-COIL GROUND-COUPLED HEAT PUMP.
  • Identifiant de la fiche : 1987-0716
  • Langues : Anglais
  • Date d'édition : 1986
  • Source : Source : ASHRAE Trans.
    vol. 92; n. 1A; 173-185; 5 fig.; 4 tabl.; 12 ref.; append.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.