PERFORMANCE D'UN DIFFUSEUR LINEAIRE CONTINU DANS LA ZONE INTERIEURE D'UN BUREAU OUVERT.

THE PERFORMANCE OF A CONTINUOUS LINEAR DIFFUSER IN THE INTERIOR ZONE OF AN OPEN OFFICE ENVIRONMENT.

Auteurs : HART G. H., INT-HOUT D.

Résumé

ON A EFFECTUE DES ESSAIS DE LABORATOIRE POUR DETERMINER L'INFLUENCE DE LA MODIFICATION DE REGLAGE DE PLUSIEURS VARIABLES SUR LA PERFORMANCE D'UN SYSTEME DE DIFFUSEUR D'AIR LINEAIRE CONTINU. POUR L'ENSEMBLE DES ESSAIS, ON A MESURE LES VALEURS LOCALES DE LA TEMPERATURE ET LA VITESSE DE L'AIR AFIN DE CALCULER L'INDICE DE PERFORMANCE DE LA DIFFUSION D'AIR. D'AUTRES ESSAIS ONT ETE EFFECTUES POUR DETERMINER L'INFLUENCE D'ECRANS ACOUSTIQUES SUR LA PERFORMANCE DE LA DIFFUSION D'AIR. LES RESULTATS AMENENT A PENSER QUE L'INDICE DE PERFORMANCE N'EST QU'UN FONCTION APPROXIMATIVE DE LA CHARGE THERMIQUE ET QUE SES VALEURS DEPENDENT FORTEMENT DE L'ESPACEMENT DES DIFFUSEURS, DU DEBIT VOLUMETRIQUE DE L'AIR ET DE LA DIFFERENCE DE TEMPERATURE ENTRE L'AIR DU LOCAL ET L'AIR SOUFFLE. LA PERFORMANCE DU DIFFUSEUR LINEAIRE CONTINU ETAIT EXCELLENTE POUR UNE GRANDE SERIE DE DIFFERENCES DE TEMPERATURE ET DE DEBITS D'AIR VOLUMETRIQUES. LA PRESENCE ES D'AIR, REDUISAIT LEGEREMENT LA PERFORMANCE DE LA DIFFUSION D'AIR.

Détails

  • Titre original : THE PERFORMANCE OF A CONTINUOUS LINEAR DIFFUSER IN THE INTERIOR ZONE OF AN OPEN OFFICE ENVIRONMENT.
  • Identifiant de la fiche : 1984-1142
  • Langues : Anglais
  • Date d'édition : 1981
  • Source : Source : ASHRAE Trans.
    vol. 87; n. 2; 311-320; 4 fig.; 1 tabl.; 9 ref.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.