Document IIF
Pompe à chaleur à absorption à ammoniac/eau de faible puissance pour le chauffage et le refroidissement.
Small-capacity ammonia/water absorption heat pump for heating and cooling.
Auteurs : MOSER H., RIEBERER R., BÖCK M.
Résumé
This paper describes the system layout, mathematical model and first experimental results of a small-capacity ammonia/water absorption heat pumping unit (cooling capacity 5 kW) which is designed for both heating and cooling purpose and shall be driven by a biomass boiler in order to reduce the energy demand as well as to increase the share of renewables in the cooling/refrigeration sector. In order to reduce the first costs standard plate heat exchangers has been used for all heat exchangers including absorber and generator. For purification of the refrigerant a rectification column with a dephlegmator cooled by the rich solution has been developed and installed downstream the generator. The COPH of the mathematical model varies approximately linear from about 1.75 to 1.4 for a temperature lift of 10 to 50 K. The experimental results show a similar correlation but approximately 7.5% below the results of the mathematical model for COPH.
Documents disponibles
Format PDF
Pages : ICR07-E2-1093
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Small-capacity ammonia/water absorption heat pump for heating and cooling.
- Identifiant de la fiche : 2007-2286
- Langues : Anglais
- Source : ICR 2007. Refrigeration Creates the Future. Proceedings of the 22nd IIR International Congress of Refrigeration.
- Date d'édition : 21/08/2007
Liens
Voir d'autres communications du même compte rendu (839)
Voir le compte rendu de la conférence
Indexation
-
Modelling and experimental analysis of a GAX NH...
- Auteurs : APRILE M., SCOCCIA R., TOPPI T., et al.
- Date : 06/2016
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 66
- Formats : PDF
Voir la fiche
-
Biomass-driven small-capacity ammonia/water abs...
- Auteurs : MOSER H., RIEBERER R.
- Date : 2007
- Langues : Anglais
- Source : IEA HPC Newsl. - vol. 25 - n. 4
Voir la fiche
-
Experimental analysis of a small-capacity ammon...
- Auteurs : ZOTTER G., RIEBERER R.
- Date : 02/03/2014
- Langues : Anglais
- Source : International sorption heat pump conference (ISHPC2014), College Park, United States, March 31-April 2, 2014.
- Formats : PDF
Voir la fiche
-
Experimental analysis of a novel concept of a “...
- Auteurs : ZOTTER G., RIEBERER R.
- Date : 12/2015
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 60
- Formats : PDF
Voir la fiche
-
Pompe à chaleur à haute température à ammoniac-...
- Auteurs : MOROZÛK L. I., MOROZÛK T. V.
- Date : 2000
- Langues : Russe
- Source : Vestnik Mezdunarodarnoj Akademii Holoda - n. 3
Voir la fiche