Pompe à chaleur air-eau en remplacement des chaudières au fioul dans un immeuble d’habitation non rénové des années 1970 : surveillance in-situ, bilan énergétique réel et performances.

Air-to-water heat pumps as a substitution of oil-boiler in a non-retrofitted multi-family building of the 70’s. In-situ monitoring, actual energy balance and performance.

Numéro : No 255

Auteurs : MONTERO O. D., FRAGA C., CALLEGARI S., HOLLMULLER P.

Résumé

In Geneva, CO2 emissions are mainly related to the heat supply in the residential sector, in particular in multifamily buildings (MFB). In this context, air-source heat pumps (HP) could help to reduce emissions and replace fossil-based heating systems, especially in dense existing urban areas where air is the only available renewable energy source. This study concerns the analysis of an existing non-retrofitted MF building of 1972 (4´047 m2 heated area), whose original fossil heat supply was recently replaced by two industrial air-to-water HPs (2 x 140 = 280 kW). Based on a detailed monitoring campaign covering 15 months of operation, the main findings show that the HP system was able to cover the entire heat demand, except for a short breakdown. Thanks to optimizations in the system regulation and the choice to use only one HP in summer, the COPsys increased from 1.3 in the early stage, up to 3.4 during the last summer. Based on the latter performances, we estimated that the SPF could reach an annual value of 2.3 (instead of the measured value of 1.9).

Documents disponibles

Format PDF

Pages : 10 p.

Disponible

Gratuit

Détails

  • Titre original : Air-to-water heat pumps as a substitution of oil-boiler in a non-retrofitted multi-family building of the 70’s. In-situ monitoring, actual energy balance and performance.
  • Identifiant de la fiche : 30030065
  • Langues : Anglais
  • Sujet : Technologie
  • Source : 13th IEA Heat Pump Conference 2021: Heat Pumps – Mission for the Green World. Conference proceedings [full papers]
  • Date d'édition : 31/08/2021

Liens


Voir d'autres communications du même compte rendu (198)
Voir le compte rendu de la conférence