Document IIF

Pompe à chaleur transcritique au CO2 à usage domestique.

Transcritical CO2 heat pump for residential application.

Auteurs : RICHTER M. R., SONG S. M., YIN J. M., et al.

Résumé

The paper describes experiments comparing a commercially available R410A heat pump and prototype R744 (carbon dioxide) system, in heating mode. The R744 system utilizes aluminium microchannel heat exchangers and a prototype semi-hermetic compressor. System performance is compared for two configurations: first when the R744 compressor speed is set to match heating capacity at 8.2 °C outdoors and 21.1 °C indoors; and second when the air conditioning capacity is matched at 35 °C outdoors and 26.5 °C indoors. The R744 system operates with a slightly lower heat performance factor, but its higher capacity at lower outdoor temperatures reduces the need for less efficient backup heating capacity.

Documents disponibles

Format PDF

Pages : 2000-1

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Transcritical CO2 heat pump for residential application.
  • Identifiant de la fiche : 2002-0044
  • Langues : Anglais
  • Source : Final proceedings of the 4th IIR-Gustav Lorentzen Conference on Natural Working Fluids at Purdue.
  • Date d'édition : 25/07/2000

Liens


Voir d'autres communications du même compte rendu (65)
Voir le compte rendu de la conférence