Document IIF

Prévision de la performance de batteries de refroidissement d'air en régime humide ou partiellement humide à l'aide de la méthode des températures équivalentes de bulbe sec.

Prediction of air coil performance under partially wet and totally wet cooling conditions using equivalent dry-bulb temperature method.

Auteurs : WANG J., HIHARA E.

Type d'article : Article, Article de la RIF

Résumé

This paper mainly deals with the cooling and dehumidifying performance of air coils used in refrigeration and air-conditioning systems. A new method, equivalent dry-bulb temperature (EDT) method, is proposed for calculating the heat and mass transfer and for predicting the cooling modes (totally wet, partially wet, and totally dry) of moist air over the coil surface. A numeric model is further developed and validated with the experimental data of plain fin air coils. The deviation in both the cooling capacity and the vapour condensate estimated by the model is within the range of ±10%, and the prediction for the cooling modes of moist air over the coil surfaces is fairly exact.

Documents disponibles

Format PDF

Pages : 293-301

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Prediction of air coil performance under partially wet and totally wet cooling conditions using equivalent dry-bulb temperature method.
  • Identifiant de la fiche : 2003-1663
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 26 - n. 3
  • Date d'édition : 05/2003

Liens


Voir d'autres articles du même numéro (10)
Voir la source