IIR document

Prediction of air coil performance under partially wet and totally wet cooling conditions using equivalent dry-bulb temperature method.

Author(s) : WANG J., HIHARA E.

Type of article: Article, IJR article

Summary

This paper mainly deals with the cooling and dehumidifying performance of air coils used in refrigeration and air-conditioning systems. A new method, equivalent dry-bulb temperature (EDT) method, is proposed for calculating the heat and mass transfer and for predicting the cooling modes (totally wet, partially wet, and totally dry) of moist air over the coil surface. A numeric model is further developed and validated with the experimental data of plain fin air coils. The deviation in both the cooling capacity and the vapour condensate estimated by the model is within the range of ±10%, and the prediction for the cooling modes of moist air over the coil surfaces is fairly exact.

Available documents

Format PDF

Pages: 293-301

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Prediction of air coil performance under partially wet and totally wet cooling conditions using equivalent dry-bulb temperature method.
  • Record ID : 2003-1663
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 26 - n. 3
  • Publication date: 2003/05

Links


See other articles in this issue (10)
See the source