PREVISION DE LA PERFORMANCE DU RECUPERATEUR DE CHALEUR ET DE MASSE A L'AIDE DE LA METHODE ANALOGIQUE NON LINEAIRE. 1. BASE. 2. COMPARAISON DE METHODES.

PREDICTION OF HEAT AND MASS REGENERATOR PERFORMANCE USING NONLINEAR ANALOGY METHOD. 1. BASIS. 2. COMPARISON OF METHODS.

Auteurs : BANKS P. J.

Type d'article : Article

Résumé

LE TRANSFERT DE CHALEUR ET DE MASSE ENTRE DES COURANTS DE FLUIDE PAR UN RECUPERATEUR AVEC UNE MATRICE DE SORBANT PEUT ETRE PREVU PAR LA SUPERPOSITION DE DEUX RECUPERATEURS INDEPENDANTS, DANS CHACUN DESQUELS LE TRANSFERT EST ENTRAINE PAR UN POTENTIEL COMBINE ANALOGUE A LA TEMPERATURE DANS UN RECUPERATEUR SEMBLABLE NE TRANSFERANT QUE DE LA CHALEUR. ON EXAMINE LES POTENTIELS COMBINES ET LES CHALEURS MASSIQUES ASSOCIEES AINSI QUE LA NATURE DE L'ANALOGIE EXPLOREE EN RAISON DE L'INFLUENCE DE L'ETAT SUR LES PROPRIETES DE SORPTION DE LA MATRICE. POUR UN RECUPERATEUR D'ENERGIE, ON MONTRE QUE LA METHODE ANALOGIQUE LINEAIRE EST SATISFAISANTE, TANDIS QU'IL FAUT UNE METHODE NON LINEAIRE POUR UN DESHUMIDIFICATEUR A RECUPERATION. ON DECRIT UNE METHODE NON LINEAIRE ET ON LA COMPARE AVEC LA PRECEDENTE METHODE NON LINEAIRE QUE L'ON MONTRE ETRE PARTIELLEMENT LINEAIRE. LES SOURCES D'ERREUR SONT EXPLOREES POUR UN DESHUMIDIFICATEUR A GEL DE SILICE ET L'ON INDIQUE LES FACONS DE L'AMELIORER.

Détails

  • Titre original : PREDICTION OF HEAT AND MASS REGENERATOR PERFORMANCE USING NONLINEAR ANALOGY METHOD. 1. BASIS. 2. COMPARISON OF METHODS.
  • Identifiant de la fiche : 1986-0381
  • Langues : Anglais
  • Source : J. Heat Transf. - vol. 107 - n. 1
  • Date d'édition : 02/1985
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.