Proposition de méthode d'évaluation des compresseurs centrifuges.
A proposed centrifugal refrigeration compressor rating method.
Numéro : pap. n. C10, 1351
Auteurs : BRASZ J. J.
Résumé
There are currently no test codes and performance standards available for rating of centrifugal refrigeration compressors, like the ANSI/ARI standard 540 for positive displacement refrigerant compressors. The reason for this lack of a standard is the fact that until recently centrifugal compressors were not sold separately but always as part of a centrifugal chiller package. The need of the end customer could be met with ARI standard 550-590 that specifies how to measure chiller performance and ASHRA standard 90.1 that dictates minimum chiller efficiency requirements. With centrifugal refrigeration compressor manufacturers offering stand-alone compressors to OEM’s for new chiller development duty as well as retrofit applications, a need for standards on how to test and rate centrifugal refrigeration compressors as individual components has surfaced. This paper discusses the issues involved in representing the performance of centrifugal refrigeration compressors for water- and air-cooled chiller duty. The polynomial performance representation of positive displacement compressors as prescribed by the positive displacement refrigeration compressor standard ANSI/ARI 540 fails to accurately describe centrifugal compressor behavior. The ASME-PTC10 power test code for centrifugal and axial compressor, used extensively by manufacturers serving the air compression and the petrochemical industry, is a more appropriate testing code for centrifugal compresors but is limited in scope to the aerodynamic performance of the compressor, neglecting mechanical, electrical and motor/inverter cooling losses important for the overall efficiency of a refrigeration compressor. An extension of the ASME PTC-10 code to include these effect is required for rating centrifugal refrigeration compressors installed on closed loop chillers.
Documents disponibles
Format PDF
Pages : 7 p.
Disponible
Prix public
20 €
Prix membre*
15 €
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : A proposed centrifugal refrigeration compressor rating method.
- Identifiant de la fiche : 30001343
- Langues : Anglais
- Sujet : Réglementation
- Source : 2010 Purdue Conferences. 20th International Compressor Engineering Conference at Purdue.
- Date d'édition : 12/07/2010
Liens
Voir d'autres communications du même compte rendu (31)
Voir le compte rendu de la conférence
Indexation
-
Low GWP chillers development.
- Auteurs : ACHAICHIA N., MATTEO G.
- Date : 12/06/2015
- Langues : Anglais
- Source : Le ultime tecnologie del freddo e del condizionamento. Atti del 16° Convegno Europeo: June 12-13, 2015, Milano, Italia.
- Formats : PDF
Voir la fiche
-
Consistent initialization of system of differen...
- Auteurs : LI P., LI Y., SEEM J. E.
- Date : 12/07/2010
- Langues : Anglais
- Source : 2010 Purdue Conferences. 20th International Compressor Engineering Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Energy saving effect of high-efficiency technol...
- Auteurs : FUKUZAKI T., AKASHI Y., MIYATA M., et al.
- Date : 27/07/2009
- Langues : Anglais
Voir la fiche
-
Modelica based dynamic modeling of water-cooled...
- Auteurs : LI P., LI Y., SEEM J. E.
- Date : 12/07/2010
- Langues : Anglais
- Source : 2010 Purdue Conferences. 13th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
The technology of high efficiency R134a two-sta...
- Auteurs : LIU C. C., CHIANG C. P., CHIANG H. C., et al.
- Date : 20/05/2009
- Langues : Anglais
- Source : ACRA-2009. The proceedings of the 4th Asian conference on refrigeration and air conditioning: May 20-22, 2009, Taipei, R.O.C.
- Formats : PDF
Voir la fiche