QUALITE DE L'AIR ET SYMPTOMES DANS UN IMMEUBLE MALSAIN ABRITANT UNE BIBLIOTHEQUE AVEC UN SYSTEME DE VENTILATION A AIR REPRIS.

AIR QUALITY AND SYMPTOMS IN A SICK LIBRARY BUILDING WITH A RETURN-AIR VENTILATION SYSTEM.

Auteurs : BERGLUND B.

Résumé

DANS UN IMMEUBLE ABRITANT UNE BIBLIOTHEQUE, CONSTRUIT 5 ANS AUPRAVANT ET D'UNE BONNE EFFICACITE ENERGETIQUE, ON A ETUDIE LA QUALITE CHIMIQUE DE L'AIR ET LES DIFFERENTS SYMPTOMES PAR RAPPORT A L'IMPACT DE L'UTILISATION QUOTIDIENNE DE L'IMMEUBLE, SUR UNE PERIODE DE 8 MOIS, AINSI QUE L'UTILISATION DE LA VENTILATION AVEC OU SANS REPRISE D'AIR. LES RESULTATS ONT ETE : (A) LES COMPOSES ORGANIQUES VOLATILS DE L'INTERIEUR ONT CONSIDERABLEMENT VARIE PENDANT LES 8 MOIS, ESSENTIELLEMENT A CAUSE DES VALEURS EXTERIEURES ; (B) 3 COMPOSES ORGANIQUES VOLATILS, DONT LA CONCENTRATION AUGMENTE NOTABLEMENT DU MATIN A L'APRES-MIDI, ONT ETE IDENTIFIES : TOLUENE, L,L,L-TRICHLOROETHANE ET LIMONENE ; (C) PARMI LES 16 SYMPTOMES RAPPORTES PAR LES VISITEURS, ON A CONSTATE QUE 8 AUGMENTAIENT BEAUCOUP DU MATIN A L'APRES-MIDI ; (D) DANS 75 % DES CAS, LA QUANTITE DE COMPOSES ORGANIQUES VOLATILS, DANS LES CONDITIONS DE FONCTIONNEMENT AVEC NS DE FONCTIONNEMENT SANS REPRISE D'AIR.

Détails

  • Titre original : AIR QUALITY AND SYMPTOMS IN A SICK LIBRARY BUILDING WITH A RETURN-AIR VENTILATION SYSTEM.
  • Identifiant de la fiche : 1990-2078
  • Langues : Anglais
  • Date d'édition : 01/08/1989
  • Source : Source : CLIMA 2000, Sarajevo
    vol. 3; 13-18; 3 fig.; 3 tabl.; 10 ref.