Résumé
Refrigerant mixtures are commonly regarded as a potential substitute in heat pumps. Two-stage compression is widely applied for improving the performance of heat pumps. The suction volume ratio is a critical design parameter for two-stage heat pumps. In this work, the optimal volume ratio of R32/R1234ze(E) mixture and 26 refrigerants named by ASHRAE Standard 34-2013 are estimated. The obtained result indicates that, for R32/R1234ze(E) mixtures, the optimal volume ratio first decreases and then increases as the R32 component increases, and the optimal volume ratio of flash tank system is lower than the intermediate heat exchanger system owing to component shifting in the flash tank. For estimated 26 refrigerants, the optimal volume ratio of the majority of zeotropic refrigerants is smaller than pure refrigerants and azeotropic refrigerants. In addition, a modified arithmetic mean temperature method is proposed to predict the optimal intermediate refrigerant states.
Documents disponibles
Format PDF
Pages : 343-353
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Optimal volume ratio of two-stage vapour compression system using zeotropic refrigerant.
- Identifiant de la fiche : 30025406
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 98
- Date d'édition : 02/2019
- DOI : http://dx.doi.org/10.1016/j.ijrefrig.2018.11.021
Liens
Voir d'autres articles du même numéro (51)
Voir la source
Indexation
-
Thèmes :
Systèmes à compression;
HFC;
Mélanges - Mots-clés : R32; R1234ze(E); Système biétage; Système à compression; Pompe à chaleur; Modélisation; Mélange zéotropique; Mélange
-
Numerical research on R32/R1234ze(E) air source...
- Auteurs : CHENG Z., WANG B., SHI W., et al.
- Date : 10/2017
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 82
- Formats : PDF
Voir la fiche
-
Effects of economizer type and size to the gas ...
- Auteurs : CHENG Z., WANG B., SHI W., et al.
- Date : 09/07/2018
- Langues : Anglais
- Source : 2018 Purdue Conferences. 24th International Compressor Engineering Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Optimal volume ratio of two stage rotary compre...
- Auteurs : CHENG Z., WANG B., SHI W., et al.
- Date : 09/2018
- Langues : Anglais
- Source : 1st IIR international conference on the application of HFO refrigerants, Birmingham, September 2-5 2018.
- Formats : PDF
Voir la fiche
-
Optimal volume ratio of two stage rotary compre...
- Auteurs : CHENG Z., WANG B., SHI W., et al.
- Date : 09/2018
- Langues : Anglais
- Source : 1st IIR international conference on the application of HFO refrigerants, Birmingham, September 2-5 2018.
- Formats : PDF
Voir la fiche
-
Exergy analysis of vapour injection system with...
- Auteurs : CHENG Z., WANG B., SHI W., et al.
- Date : 24/08/2019
- Langues : Anglais
- Source : Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
- Formats : PDF
Voir la fiche