Recherche expérimentale sur les mélanges de frigorigènes d'un système frigorifique Linde-Hampson.

[In Chinese. / En chinois.]

Auteurs : ZHU J., ZHANG H.

Type d'article : Article

Résumé

The performance of quatemionic refrigerant mixtures, R34Sfa/R600a/R508b/R14, in Linde-Hampson refrigeration cycle was experimentally investigated. To get the lowest operation temperature, the components of refrigerant mixtures were optimized. The influence of ambient temperature on system operational performance was analyzed. It is shown that the lowest system operation temperature could reach from -45°C to -85°C when mixing the four refrigerant components at different species ratio, If the proportion of the refrigerant mixtures charged is R24Sfa:R600a:RS08b:RI4=0.45:0.3:0.18:0.07, the operating temperature of the system can reach -85°C when the ambient temperature is 35°C. With the same refrigerant mixtures, the system temperature can reach -89.3°C if the ambient temperature decreases from 35°C to 5°C.

Documents disponibles

Format PDF

Pages : 18-23

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : [In Chinese. / En chinois.]
  • Identifiant de la fiche : 30005195
  • Langues : Chinois
  • Source : Journal of Refrigeration - vol. 33 - n. 144
  • Date d'édition : 04/2012