Recherches sur la consommation d'énergie des pompes à vitesse variable dans les systèmes de conditionnement d'air.

Research on energy consumption of variable-frequency chilled water pumps in air-conditioning systems.

Auteurs : WANG H. D.

Résumé

Based on the fact that chilled water loop resistance varies with the air-conditioning loads, a general formula of the energy consumption of variable-frequency chilled water pumps in a primary system is obtained. Analysis shows that pump's affinity laws cannot be directly applied to determine the energy consumption of variable-frequency chilled water pumps and the consumed energy is not proportional to the cube of pump speed, but varies with the constant-differential-pressure water-head, air-conditioning loads, capacity distribution characteristics or the locations of air-handling units and the resistance coefficient of the chilled water loop.

Détails

  • Titre original : Research on energy consumption of variable-frequency chilled water pumps in air-conditioning systems.
  • Identifiant de la fiche : 2006-2572
  • Langues : Anglais
  • Source : Cryogenics and refrigeration. Proceedings of ICCR 2003.
  • Date d'édition : 22/04/2003

Liens


Voir d'autres communications du même compte rendu (166)