Document IIF

Refroidissement évaporatif au dioxyde de carbone pour l'amélioration des détecteurs au LHC (grand collisionneur de particules).

Evaporative cooling with carbon dioxide for the detectors upgrade at the Large Hadron Collider.

Auteurs : ORIUNNO M., CEPEDA M., CONVERY M., et al.

Résumé

Carbon dioxide is a very attractive refrigerant for scientific instruments where low mass and radiation hardness are required. In the context of the ATLAS Tracker upgrade for the Large Hadron Collider, the authors designed a local support structure with the cooling channel optimized for a two-phase flow of carbon dioxide. The prototype has been thermally characterized with a scalable and low-cost evaporative plant operated in open cycle (blow system). The temperature gradients are compared with measurements done with water at room temperature and with finite element models. A preliminary estimation of the heat transfer coefficients is provided.

Documents disponibles

Format PDF

Pages : 2010-2

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Evaporative cooling with carbon dioxide for the detectors upgrade at the Large Hadron Collider.
  • Identifiant de la fiche : 2010-1359
  • Langues : Anglais
  • Source : 9th IIR-Gustav Lorentzen Conference on Natural Working Fluids (GL2010). Proceedings. Sydney, Australia, April 12-14, 2010.
  • Date d'édition : 12/04/2010

Liens


Voir d'autres communications du même compte rendu (84)
Voir le compte rendu de la conférence