Refroidissement sous plancher dans les bâtiments de type nZEB.

Under floor cooling in nZEB.

Numéro : pap. n. 103

Auteurs : SØNDERBY NIELSEN L., HANSEN J., KOJO M., et al.

Résumé

Low Energy construction methods typically imply that significant cooling loads are introduced. Building simulations as well as experiences from real houses have indicated cooling loads of up to 40 W/m2 in Northern European climatic conditions. The paper reviews measured and simulated results of the cooling loads introduced in nZEB buildings. To meet the cooling loads in a sustainable way it is suggested to use under-floor cooling with a ground heat exchanger as a heat sink. The solution has been implemented and measured using vertical as well as horizontal ground heat exchangers. The results show that such under-floor cooling systems ensure indoor temperatures below 26 °C in all cases regardless of the seasons.