Document IIF
Refroidisseur d'eau avec compresseur centrifuge sans huile.
Water chiller with oil-free centrifugal compressors.
Auteurs : MINEA V.
Résumé
This paper deals with energy performances of a 440-kW (125-ton) air-conditioning factory-assembled water chiller with totally oil-free, variable speed centrifugal compressors and air-cooled condensers. The prototype was installed in Montreal (Eastern Canada) in a retrofit building with telecommunication equipment, process computers and other similar cooling charges. The non-standard part load values (NPLV) are calculated during a typical summer Canadian weather period. This study demonstrates that magnetic bearings, variable-speed compression and digital electronic controls achieve high compressor efficiencies with air-cooled water chillers. For the retrofit system having a very constant process cooling charge, the average seasonal NPLV is 49% lower as compared to previous existing conventional air-cooled chillers. The mechanical room noise is also significantly diminished, while the simple pay-back period is estimated at 3.5 years (without subsides) for a technical life of 25 year.
Documents disponibles
Format PDF
Pages : 2006-5
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Water chiller with oil-free centrifugal compressors.
- Identifiant de la fiche : 2007-0166
- Langues : Anglais
- Source : Compressors 2006: 6th International Conference on Compressors and Coolants
- Date d'édition : 27/09/2006
Liens
Voir d'autres communications du même compte rendu (48)
Voir le compte rendu de la conférence
Indexation
-
Thèmes :
Autres équipements de conditionnement d'air;
Compresseurs;
Circulation du fluide : tuyauterie, régulation, automatisme, sécurité - Mots-clés : Électronique; Vitesse variable; Régulation; Refroidisseur; Palier; Performance; Magnétisme; Conditionnement d'air; Compresseur sec; Compresseur centrifuge
-
Performance of variable speed centrifugal chill...
- Auteurs : MULUGETA J., DIETRICH W.
- Date : 23/07/1996
- Langues : Anglais
- Source : Proceedings of the 1996 International Compressor Engineering Conference at Purdue.
Voir la fiche
-
Temperature-dependent thermodynamic chiller mod...
- Auteurs : LIU C. C., CHUNG J. C., CHIANG H. C., et al.
- Date : 07/06/2010
- Langues : Anglais
- Source : ACRA2010. Asian conference on refrigeration and air conditioning: Tokyo, Japan, June 7-9, 2010.
- Formats : PDF
Voir la fiche
-
Performance analysis of a variable speed drive.
- Auteurs : OSSORIO R., NAVARRO E., LÓPEZ A., ROMAN J. A. M.
- Date : 11/11/2020
- Langues : Anglais
- Source : X Congreso Ibérico y VIII Congreso Iberoamericano de Ciencias y Técnicas del Frío, CYTEF 2020.
- Formats : PDF
Voir la fiche
-
Optimisation énergétique de refroidisseurs d'ea...
- Auteurs : BACIGALUPO E. G.
- Date : 29/03/1996
- Langues : Italien
- Source : Condizionamento, riscaldamento, refrigerazione: innovazioni e tendenze. 37e Convegno annuale AICARR./ Air Conditioning, Heating and Refrigeration: Innovations and Trends. 37th annual conference of AICARR.
Voir la fiche
-
Analyse et application d'une méthode d'évaluati...
- Auteurs : ZHANG H., WU J., LI Y.
- Date : 02/2013
- Langues : Chinois
- Source : Journal of Refrigeration - vol. 34 - n. 149
- Formats : PDF
Voir la fiche