Document IIF

Régénérateur magnétique actif et rotatif innovant : résultats expérimentaux.

Experimental results for a novel rotary active magnetic regenerator.

Auteurs : ENGELBRECHT K., ERIKSEN D., BAHL C. R. H., et al.

Type d'article : Article, Article de la RIF

Résumé

Active magnetic regenerator (AMR) refrigerators represent an alternative to vapor compression technology and have great potential in realizing cooling devices with high efficiency, which are highly desirable for a broad range of applications. The technology relies on the magnetocaloric effect in a solid refrigerant rather than the temperature change that occurs when a gas is compressed/expanded. This paper presents the general considerations for the design and construction of a high frequency rotary AMR device. Experimental results are presented at various cooling powers for a range of operating conditions near room temperature. The device exhibited a no-load temperature span of over 25 K and can absorb a 100 W cooling load at a 20.5 K temperature span.

Documents disponibles

Format PDF

Pages : 1498-1505

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental results for a novel rotary active magnetic regenerator.
  • Identifiant de la fiche : 30004788
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 35 - n. 6
  • Date d'édition : 09/2012

Liens


Voir d'autres articles du même numéro (28)
Voir la source