Document IIF

Régulation optimale d'un système de conditionnement d'air combiné avec débit variable de frigorigène et volume d'air variable pour économiser l'énergie.

Optimal control of combined air conditioning system with variable refrigerant flow and variable air volume for energy saving.

Auteurs : ZHU Y., JIN X., FANG X., et al.

Type d'article : Article, Article de la RIF

Résumé

An optimal control strategy for minimizing the energy consumption of variable refrigerant flow (VRF) and variable air volume (VAV) combined air conditioning systems was presented. The combined system was proposed to take advantages of VAV systems to solve the ventilation problem of VRF systems. The VAV part consists of an outdoor air processing unit and air supply and distribution devices. To determine set-point of the optimal control variable, i.e. outdoor air supply temperature, this paper proposed an optimal control strategy based on adaptive predictive model and recursive least squares estimation technique. Typical days in summer and winter were selected to test the strategy. Results indicated that the optimal control strategy reduces energy consumption of the combined system by 32.17% in summer and 2.47% in winter. The overall energy efficiency is enlarged by 12.18% in summer and 3.37% in winter, compared with the benchmark operation strategy.

Documents disponibles

Format PDF

Pages : 14-25

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Optimal control of combined air conditioning system with variable refrigerant flow and variable air volume for energy saving.
  • Identifiant de la fiche : 30011394
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 42
  • Date d'édition : 06/2014

Liens


Voir d'autres articles du même numéro (12)
Voir la source