Document IIF
Remplacement du R404A à température de condensation élevée par le R454C et le R455A.
Replacement of R404A at high condensation temperature using R454C and R455A.
Numéro : pap. n. 1152
Auteurs : HARO ORTUNO J., MOTA BABILONI A., NAVARRO-ESBRÍ J., et al.
Résumé
R404A must be replaced for all commercial refrigeration applications following the instructions of the European F-gas Regulation. The recently developed mixtures R454C and R455A offer Global Warming Potential below 150, solutions with an ASHRAE 34 flammability classification of A2L. This paper presents and compares the experimental results of a refrigeration system using R404A, R454C and R455A, at a condensation temperature of 47 °C and evaporation temperatures of -13 and -30 °C. The experimental results show that, when using the alternative refrigerants instead of R404A, the refrigerating effect is increased, but the compressor suction density is lower. While the volumetric cooling capacity of R455A is comparable, that of R454C is lower than R404A. The coefficient of performance with both alternatives is significantly higher, so there is an energetic and hence environmental benefit from their utilization. The discharge temperature is within the limits, but it can be a limitation in higher compression ratios. The drop-in replacement only required adjustments in the TXV screw and in the refrigerant charge.
Documents disponibles
Format PDF
Pages : 8
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Replacement of R404A at high condensation temperature using R454C and R455A.
- Identifiant de la fiche : 30024848
- Langues : Anglais
- Source : 1st IIR international conference on the application of HFO refrigerants, Birmingham, September 2-5 2018.
- Date d'édition : 09/2018
- DOI : http://dx.doi.org/10.18462/iir.hfo.2018.1152
Liens
Voir d'autres communications du même compte rendu (126)
Voir le compte rendu de la conférence
Indexation
-
Thèmes :
HFC;
Supermarchés, meubles de vente - Mots-clés : R454C; Application commerciale; Faible GWP; Remplacement immediat; R455A; R404A; Puissance frigorifique; Supermarché; Experimentation; COP
-
Replacement of R404A at high condensation tempe...
- Auteurs : HARO ORTUNO J., MOTA BABILONI A., NAVARRO-ESBRÍ J., et al.
- Date : 09/2018
- Langues : Anglais
- Source : 1st IIR international conference on the application of HFO refrigerants, Birmingham, September 2-5 2018.
- Formats : PDF
Voir la fiche
-
Development of low global warming potential ref...
- Auteurs : ABDELAZIZ O., FRICKE B., VINEYARD E.
- Date : 16/07/2012
- Langues : Anglais
- Source : 2012 Purdue Conferences. 14th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Evaluación energética del refrigerante R468A co...
- Auteurs : CABELLO LÓPEZ R., GARCIA-VACAS D. S., NEBOT-ANDRÉS L., CALLEJA-ANTA D., LLOPIS DOMÉNECH R.
- Date : 11/11/2020
- Langues : Espagnol
- Source : X Congreso Ibérico y VIII Congreso Iberoamericano de Ciencias y Técnicas del Frío, CYTEF 2020.
- Formats : PDF
Voir la fiche
-
Low and ultra-low GWP refrigerants to replace R...
- Auteurs : SAN ROMÁN M., ACHAICHIA N.
- Date : 03/05/2016
- Langues : Anglais
- Source : CYTEF 2016. VIII Congreso Ibérico y VI Congreso Iberoamericano de las Ciencias y Técnicas del Frío, Coimbra-Portugal, 3-6 mayo, 2016.
- Formats : PDF
Voir la fiche
-
Low global warming refrigerants for commercial ...
- Auteurs : YANA MOTTA S., SPATZ M. W., VERA BECERRA E.
- Date : 16/07/2012
- Langues : Anglais
- Source : 2012 Purdue Conferences. 14th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche