REPENSER LE TRAITEMENT DES TOURS DE REFROIDISSEMENT.

RETHINKING COOLING TOWER TREATMENT.

Type d'article : Article

Résumé

ON DECRIT UNE NOUVELLE APPROCHE POUR PREVENIR L'APPARITION DE LA LEGIONELLOSE CAUSEE PAR LES TOURS DE REFROIDISSEMENT HUMIDES. COMME IL EST IMPOSSIBLE D'ERADIQUER LES BACTERIES LEGIONELLA, IL CONVIENT DE CREER UN ENVIRONNEMENT QUI LEUR SOIT HOSTILE. ON RAPPORTE DES RECHERCHES SUR L'EFFET DU PH DE L'EAU DANS LA TOUR DE REFROIDISSEMENT, ET ON A OBSERVE QUE LES BACTERIES ETAIENT SEVEREMENT AFFAIBLIES A UN PH ELEVE, CE QUI REND L'ACTION D'UN BIOCIDE BEAUCOUP PLUS FACILE. ON NOTE QUE LES TOURS DE REFROIDISSEMENT EN ACIER, DU TYPE COMMUNEMENT UTILISE POURLES APPLICATIONS DU CONDITIONNEMENT D'AIR, NE SONT STABLES QUE POUR UN PH COMPRIS ENTRE 7 ET 8. EN DEHORS DE CETTE PLAGE, IL FAUT UTILISER DES TOURS DE REFROIDISSEMENT DE DIFFERENTS MATERIAUX ; CERTAINES SONT D'ORES ET DEJA PRODUITES, QUI SONT STABLES JUSQU'A UN PH EGAL A 11. (INT. BUILD. SERV. ABSTR., GB., 25, N 6, 1990/11-12, 90-01879.

Détails

  • Titre original : RETHINKING COOLING TOWER TREATMENT.
  • Identifiant de la fiche : 1991-2573
  • Langues : Anglais
  • Date d'édition : 1990
  • Source : Source : Build. Serv. environ. Eng.
    vol. 13; n. 1; 1990.09; 16-17; 2 fig.