Document IIF
Simulation du processus d'arrêt d'une installation frigorifique munie d'un compresseur à deux vis.
Shutdown process simulation of a refrigeration plant having a twin scew compressor.
Auteurs : FLEMING J. S., TANG Y., YOU C. X.
Type d'article : Article, Article de la RIF
Résumé
In twin screw compressor plants of a certain configuration the suction non-return valve was removed and a reverse rotation brake was fitted to the free end of the motor shaft to prevent backflow of the (oil-laden) refrigerant and reverse rotation of the compressor rotors immediately following plant shutdown. Brake failures occurred on site. The paper describes one part of the subsequent investigation, namely the adaptation of a program created to calculate normal running torque to the process calculating the maximum static torque to occur following shutdown. Shutdown torques up to 60% greater than the running torque are predicted but are thought to be underestimates due to the distribution of oil following shutdown being different from that during normal operation. The authors believe that, following shutdown, the oil seals the exit leakage path across the contact line but clears away from the inlet path through the blow hole allowing unexpectedly high cavity pressures and torques to develop. In existing plants fitted with brakes chosen on the assumption that the shutdown torque will be no greater than the running torque, a safe shutdown may be obtained by opening the slide valve prior to shutdown.
Documents disponibles
Format PDF
Pages : 422-428
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Shutdown process simulation of a refrigeration plant having a twin scew compressor.
- Identifiant de la fiche : 1998-0846
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 19 - n. 6
- Date d'édition : 07/1996
Liens
Voir d'autres articles du même numéro (6)
Voir la source
Indexation
- Thèmes : Compresseurs
- Mots-clés : Fonctionnement; Simulation; Procédé; Installation frigorifique; Compresseur à vis
-
Development of a comprehensive thermodynamic mo...
- Auteurs : SAULS J.
- Date : 23/07/1996
- Langues : Anglais
- Source : Proceedings of the 1996 International Compressor Engineering Conference at Purdue.
Voir la fiche
-
A semi-empirical method for modelling a recipro...
- Auteurs : POPOVIC P., SHAPIRO H. N.
- Date : 24/06/1995
- Langues : Anglais
- Source : ASHRAE Transactions.
Voir la fiche
-
The use of superfeed in a refrigeration plant w...
- Auteurs : FLEMING J. S., TANG Y., XING Z. W., COOK G.
- Date : 20/08/1995
- Langues : Anglais
- Source : For a Better Quality of Life. 19th International Congress of Refrigeration.
- Formats : PDF
Voir la fiche
-
COMPRESSEURS A VIS ET EQUIPEMENTS DE CONGELATIO...
- Auteurs : KALINOWSKI K.
- Date : 07/1991
- Langues : Polonais
- Source : Chlodnictwo - vol. 26 - n. 7
Voir la fiche
-
Nonlinear modelling and observer design for the...
- Auteurs : WAGNER J., SHOURESHI R.
- Date : 1993
- Langues : Anglais
- Source : Int. J. Model. Simul. - vol. 13 - n. 1
Voir la fiche