Simulations de la puissance d'un système de refroidissement par le sol.

Simulations of floor cooling system capacity.

Auteurs : ODYJAS A., GÓRKA A.

Type d'article : Article

Résumé

Floor cooling system capacity depends on its physical and operative parameters. Using numerical simulations, it appears that cooling capacity of the system largely depends on the type of cooling loads occurring in the room. In the case of convective cooling loads capacity of the system is small. However, when radiation flux falls directly on the floor the system significantly increases productivity. The article describes the results of numerical simulations which allow to determine system capacity in steady thermal conditions, depending on the type of physical parameters of the system and the type of cooling load occurring in the room. Moreover, the paper sets out the limits of system capacity while maintaining a minimum temperature of the floor surface equal to 20°C. The results are helpful for designing system capacity in different type of cooling loads and show maximum system capacity in acceptable thermal comfort condition.

Détails


Liens


Voir d'autres articles du même numéro (26)
Voir la source