Stabilité de la régulation de la température dans des systèmes à volume d'air variable.
Stability of temperature control in VAV systems.
Auteurs : YAMAKAWA Y., YAMAZAKI T., KAMIMURA K., et al.
Résumé
Indoor air temperature control of a single zone space is studied. In air-conditioning systems, a step or an impulse in setpoint or a slight disturbance, can lead to hunting. Variable air volume (VAV) control is very common in air-conditioning systems. The supply airflow rates to the space can be controlled by motorized dampers or by fan speed control. VAV systems are assumed to be an essential source of hunting. To explore the possible connection between VAV systems and hunting, a dynamic system model is formulated as a bilinear model with time-delayed feedback (by P or PI control actions), and a parametric analysis of the stability region is presented. Results are given that show the stability region affected by the selection of setpoint values and control parameters. This analysis is conducted to help us tune proportional-integral-derivative controllers to achieve good control performance.
Détails
- Titre original : Stability of temperature control in VAV systems.
- Identifiant de la fiche : 2009-2466
- Langues : Anglais
- Source : ASHRAE Transactions. Papers presented at the 2009 ASHRAE Winter Conference: Chicago, Illinois, January 2009. Volume 115, part 1.
- Date d'édition : 25/01/2009
Liens
- Liens externes :
Voir d'autres communications du même compte rendu (20)
Voir le compte rendu de la conférence
Indexation
- Thèmes : Autres équipements de conditionnement d'air
- Mots-clés : Débit variable; Température; Régulation; Air; Stabilité; Modélisation; Conditionnement d'air
-
Stability limit of room air temperature of a VA...
- Auteurs : MATSUBA T., KASAHARA M., MURASAWA I., et al.
- Date : 1998
- Langues : Anglais
- Source : ASHRAE Transactions. 1998 annual Meeting, Toronto, Ontario + CD-ROM.
Voir la fiche
-
Stability analysis for a variable-air-volume (V...
- Auteurs : LI M., LEVERMORE G. J.
- Date : 2000
- Langues : Anglais
- Source : Build. Serv. Eng. Res. Technol. - vol. 21 - n. 4
Voir la fiche
-
A VRF charge fault diagnosis method based on ex...
- Auteurs : YU F., LI G., CHEN H., et al.
- Date : 08/2018
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 92
- Formats : PDF
Voir la fiche
-
Model-based robust temperature control for VAV ...
- Auteurs : HUANG G., JORDAN F.
- Date : 06/2012
- Langues : Anglais
- Source : HVAC&R Research - vol. 18 - n. 3
Voir la fiche
-
Modeling of variable refrigerant flow system fo...
- Auteurs : KWON L., HWANG Y., RADERMACHER R., et al.
- Date : 16/07/2012
- Langues : Anglais
- Source : 2012 Purdue Conferences. 14th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche