Stratégie intégrée permettant de diagnostiquer les anomalies des capteurs des systèmes frigorifiques d'immeubles.

An integrated robust strategy for diagnosing sensor faults in building chilling systems.

Auteurs : WANG J. B., WANG S., BURNETT J.

Type d'article : Article

Résumé

The integrated strategy, which extends the works of Wang and Wang (1999), is based on the universal conservation relationships for mass and energy. Biases in temperature sensors and flow meters are estimated by minimizing the sums of the squares of the mass and energy balance residuals. A robust approach using a genetic algorithm is used to systematically minimize the sums of the squares of the associated heat balance residuals so that the biases are estimated more reliably and accurately.

Détails

  • Titre original : An integrated robust strategy for diagnosing sensor faults in building chilling systems.
  • Identifiant de la fiche : 2003-1968
  • Langues : Anglais
  • Source : HVAC&R Research - vol. 8 - n. 2
  • Date d'édition : 04/2002
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres articles du même numéro (5)
Voir la source