Système à pompes à chaleur sol-air utilisé pour un hôtel aux Etats-Unis.
North American monitoring of a hotel with room size GSHPS (ground-source heat pump system).
Auteurs : HENDERSON H. I., CARLSON S. W., WALBURGER A. C.
Résumé
The 149-room lake front hotel has a ground loop that is partially incorporated into the building's structural pilings and a heat pump water heating system that is integrated into the ground loop of the space conditioning system. Loop temperatures are ranging between 4 and 27 °C across the year. The integration of the water heating heat pumps into the system reduced the summer heat rejection loads by more than 15%. Variable speed loop pumping dramatically reduced system energy use by 92% compared to a conventional constant speed pumping system. This system demonstrates the performance benefits of geothermal heat pump systems.
Détails
- Titre original : North American monitoring of a hotel with room size GSHPS (ground-source heat pump system).
- Identifiant de la fiche : 2001-0483
- Langues : Anglais
- Source : Heat pump systems for single-room applications. Workshop proceedings.
- Date d'édition : 17/06/1998
- Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.
Liens
Voir d'autres communications du même compte rendu (10)
Voir le compte rendu de la conférence
Indexation
-
The installation of room size ground-source hea...
- Auteurs : LENARDUZZI F. J., YOUNG D. J.
- Date : 17/06/1998
- Langues : Anglais
- Source : Heat pump systems for single-room applications. Workshop proceedings.
Voir la fiche
-
Les thermopompes à capteurs enterrés dans les r...
- Auteurs : OSSANT G.
- Date : 02/04/1997
- Langues : Français
- Source : Effet de serre, économies d'énergie.
Voir la fiche
-
Residential vertical geothermal heat pump syste...
- Auteurs : THORNTON J. W., MCDOWELL T. P., SHONDER J. A., HUGHES P. J., PAHUD D., HELLSTROEM G. A. J.
- Date : 1997
- Langues : Anglais
- Source : ASHRAE Transactions.1997 Annual Meeting, Boston, MA.
Voir la fiche
-
Evaluation of heat pumps for hotels.
- Auteurs : CANE D., MORRISON A.
- Date : 17/06/1998
- Langues : Anglais
- Source : Heat pump systems for single-room applications. Workshop proceedings.
Voir la fiche
-
Commissioning, preventive maintenance, and trou...
- Auteurs : CANE R. L. D., GARNET J. M., SACHS H. M.
- Date : 2002
- Langues : Anglais
- Source : ASHRAE Transactions. 2002 annual Meeting, Honolulu, Hawaii. Volume 108, part 2 + CD-ROM.
Voir la fiche